  "$schema": "https://verbaipsa.org/api/v1/schema/stelle.schema.json",
  "amtlich": false,
  "api_json": "/api/v1/ch/sr-734.2/art-39.de.json",
  "api_md": "/api/v1/ch/sr-734.2/art-39.de.md",
  "edition": "Fedlex, Systematische Rechtssammlung des Bundes",
  "edition_id": "fedlex-sr",
  "eid": "art_39",
  "extraktionsregel": "akn-kanon-v1",
  "fassung_kennung": "ch/sr-734.2/2019-06-01/art-39",
  "fundstelle": "https://www.fedlex.admin.ch/eli/cc/1994/1199_1199_1199/de#art_39",
  "fussnoten": [],
  "gliederung": [
    {
      "ebene": "chapter",
      "eid": "chap_3",
      "num": "3. Kapitel:",
      "titel": "Erzeugungs- und Verteilanlagen"
    },
    {
      "ebene": "section",
      "eid": "chap_3/sec_2",
      "num": "2. Abschnitt:",
      "titel": "Innenraumanlagen"
    }
  ],
  "id": "ch/sr-734.2/art-39",
  "ist_geltend": true,
  "kanonische_url": "https://verbaipsa.org/ch/sr-734.2/art-39/de/",
  "kennung": "ch/sr-734.2/art-39",
  "lizenz": "gemeinfrei, Art. 5 URG",
  "num": "Art. 39",
  "quelle_sha": "430ccc9d9b0d655f32b7b916d1ebcecf2b040f80d406ab065b191ff9c10717f9",
  "schema": 1,
  "sha256": "3f7024be0a0b009fdb20ca3199822bb6dc7ca5fef7d6ac2651f4f5babf734ce5",
  "sprache": "de",
  "sr": "734.2",
  "stand": "2019-06-01",
  "stelle": "art-39",
  "titel": "Unterirdische Anlagen",
  "typ": "stelle",
  "url": "/ch/sr-734.2/art-39/de/",
  "werk_id": "ch/sr-734.2",
  "werk_kennung": "sr-734.2",
  "werk_kurztitel": "SR 734.2",
  "werk_titel": "Verordnung über elektrische Starkstromanlagen",
  "wortlaut": "1 Unterirdische Starkstromanlagen müssen allseitig berührungssicher gebaut sein, wenn sie nur über einen vertikalen Einstieg zugänglich sind.\n2 Sind sie nicht berührungssicher, so muss für den Einstieg ein Vorraum vorgesehen werden, der vom Betriebsraum durch eine Türe abgetrennt ist."
}